Horner-apg XL4 OCS Manuel d'utilisateur

Naviguer en ligne ou télécharger Manuel d'utilisateur pour Capteurs Horner-apg XL4 OCS. Horner APG XL4 OCS User Manual [fr] Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 6
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
MAN0963-07EN
Specifications / Installation
XL4 OCS
Datasheet for
HE-XC1E0, HE-XC1E2, HE-XC1E3, HE-XC1E4, HE-XC1E5
HEXT251C100, HEXT251C112, HEXT251C113, HEXT251C114, HEXT251C115
General Specifications
Control & Logic Specifications
Required Power
(Steady state)
95 mA @ 24 VDC
190 mA @ 12 VDC
Required Power
(Inrush)
2A for <1 ms @ 24 VDC
DC Switched
Primary Power Range
10 30 VDC
Relative Humidity
5 to 95% Non-condensing
Digital Inputs
2048
Clock Accuracy
+/- 20 ppm maximum at 25° C
(+/- 1 Minutes per Month)
Digital Outputs
2048
Analog Inputs
512
Surrounding Air Temp
-10°C to +60°C
Analog Outputs
512
Storage Temp
-30°C to +70°C
Weight
12 oz. (340 g)
UL / CE
USA: http://www.heapg.com/Pages/TechSupport/ProductCert.html
Europe: http://www.horner-apg.com/en/support/certification.aspx
Display Specifications
Connectivity
Display Type
3.5” TFT Transmissive Color
Serial Ports
1 RS-232 & 1 RS-485 on single Modular Jack
Resolution
QVGA (320x240)
USB mini-B
USB 2.0 (480MHz) Programming & Data Access
Color
16-bit (65,535)
USB A
USB 2.0 (480MHz) for USB FLASH Drives (2TB)
Screen Memory
64MB
CAN
Remote I/O, Peer-to-Peer Comms, Cscape
User-Programmable
Screens
1023
Ethernet
10/100 Mb (Auto-MDX)
Modbus TCP C/S, HTTP, FTP, SMTP, Cscape
Backlight
LED 50,000 hour life
Remote I/O
SmartRail, SmartStix, SmartBlock, SmartMod
Screen Update Rate
User Configurable within the scan time.
(perceived as instantaneous in many cases)
Removable
Memory
MicroSD, support for >32GB max.
Application Updates, Datalogging, more
Input / Output Specifications
Model
DC In
DC
Out
Relays
HS In
HS Out
mA/V
In
mA/V
RTD/Tc
mA/V
Out
High-Speed Counters
Number of Counters
2
Model 2
12
6
4
4
Maximum Frequency
>500kHz each
Model 3
12
12
4
2
2
Accumulator Size
32-bits each
Model 4
24
16
4
2
2
Modes Supported
Model 5
12
12
4
2
2
2
Totalizer
Quadrature
There are 4 high-speed inputs of the total DC Inputs. There are 2 high-speed outputs of the total
DC outputs. Model 2, 3 & 4 feature 12-bit Analog I/O. Model 5 features 14/16-bit Analog I/O.
High-speed Outputs can be used for PWM and Pulse Train Outputs, currently limited to <65kHz.
Pulse Meas.
Frequency Meas.
2 Position Controlled Outputs
1 ON/OFF Setpoint per Output
1 Specifications
2 Dimensions & Panel Cutout
Cutout tolerance to meet NEMA
standards is ±
0.005 (0.1mm).
Max. Panel Thickness is 5mm.
Panel Cutout
August 23, 2012
Specifications / Installation
Page 1 of 6
3.622 [92mm]
3.622 [92mm]
001XLE002
Vue de la page 0
1 2 3 4 5 6

Résumé du contenu

Page 1 - XL4 OCS

MAN0963-07EN Specifications / Installation XL4 OCS Datasheet for HE-XC1E0, HE-XC1E2, HE-XC1E3, HE-XC1E4, HE-XC1E5 HEXT251C100, HEXT251C112, HEXT251C11

Page 2 - Locations

MAN0963-07EN Specifications / Installation August 23, 2012 Specifications / Installation Page 2 of 6 3 Installation Procedures 1. Carefully locat

Page 3 - 001XLE037-R1

MAN0963-07EN Specifications / Installation August 23, 2012 Specifications / Installation Page 3 of 6 DC Input / Frame Torque rating 4.5 – 7 Lb-In (

Page 4 - 12-24VDC

MAN0963-07EN Specifications / Installation August 23, 2012 Specifications / Installation Page 4 of 6 7 Built-in I/O (Model 2, 3, 4 & 5) Note: T

Page 5 - Jumper Setting Details

MAN0963-07EN Specifications / Installation August 23, 2012 Specifications / Installation Page 5 of 6 Model 3 & Model 4 I/O The XL4 model 3 (HE-X

Page 6

MAN0963-07EN Specifications / Installation August 23, 2012 Specifications / Installation Page 6 of 6 Model 5 I/O The XL4 model 5 (HE-XC1E5) feature

Commentaires sur ces manuels