MAN0946-01-EN Specifications / Installation
1/6/2011 Page 1 of 3
1 Specifications
Specifications
Digital DC Inputs
Digital Relay Outputs
Inputs per Module
12 including 4 configurable
HSC inputs
Outputs per Module
6 relay
Commons per Module
1
Commons per Module
6
Input Voltage Range
12 VDC / 24 VDC
Max. Output Current per Relay
3 A at 250 VAC, resistive
Absolute Max. Voltage
35 VDC Max.
Max. Total Output Current
5 A continuous
Input Impedance
10 kΩ
Max. Output Voltage
275 VAC , 30 VDC
Positive Logic
Negative Logic
Max. Switched Power
1250 VA, 150 W
0.8 mA
-1.6mA
Contact Isolation to XLe ground
1000 VAC
0.3 mA
-2.1mA
Max. Voltage Drop at Rated
Current
0.5 V
Max Upper Threshold
8 VDC
Expected Life
(See Derating section for chart.)
No load: 5,000,000
Rated load: 100,000
Min Lower Threshold
3 VDC
Max. Switching Rate
300 CPM at no load
20 CPM at rated load
OFF to ON Response
1 ms
Type
Mechanical Contact
ON to OFF Response
1 ms
Response Time
One update per ladder scan
plus 10 ms
HSC Max. Switching Rate
10 kHz Totalizer/Pulse, Edges
5 kHz Frequency/Pulse, Width
2.5 kHz Quadrature
Analog Inputs, Medium Resolution
Number of Channels
4
Input Ranges
0 - 10 VDC
0 20 mA
4 20 mA
Safe input voltage range
-0.5 V to +12V
Input Impedance
(Clamped @ -0.5 VDC to 12
VDC)
Current Mode:
100 Ω
Voltage
Mode:
500 k Ω
Nominal Resolution
10 Bits
%AI full scale
32,000 counts
Max. Over-Current
35 mA
Conversion Speed
All channels converted once per
ladder scan
Max. Error at 25°C
(excluding zero)
*can be made tighter
(~0.25%) by adjusting the
digital filter setting to 3.
4-20 mA 1.00%
0-20 mA 1.00%
0-10 VDC 1.50%*
Additional error for
temperatures other than 25° C
TBD
Filtering
160 Hz hash (noise) filter
1-128 scan digital running
average filter
2 Wiring and Jumpers
XL Series Built-in I/O Model 2 I/O
12 DC Inputs, 6 Relay Outputs, 4 Analog Inputs
for XLe, XLt, XL6 (all models) and XL10e
Wiring Specifications
For I/O wiring (discrete), use the
following wire type or equivalent: Belden
9918, 18 AWG (0.8 mm
2
) or larger.
For shielded Analog I/O wiring, use the
following wire type or equivalent: Belden
8441, 18 AWG (0.8 mm
2
) or larger.
For CAN wiring, use the following wire
type or equivalent: Belden 3084, 24
AWG (0.2 mm
2
) or larger.
Use copper conductors in field wiring
only, 60/75° C
Location of I/O jumpers
(JP1 & JP2) and
wiring connectors
(J1 and J2) with back cover
removed.
Note: The Cscape Module Setup configuration must match the
selected I/O (JP) jumper settings.
001XLE026
JP1 Digital DC In / HSC
Positive Negative
Logic Logic
Default
001XLE027
A1
A2
A3
A4
JP2 Analog In (A1 A4)
Current Voltage
(20 mA) (10 V)
Default
Note: When using JP2 (A1-A4), each channel can be
independently configured.
Jumper Setting Details