MAN0884-04-EN Specifications / Installation
__________________________________________________________________________________________________________________________________________________________________________
3/2/2010 Page 1 of 4 #1037
1 Specifications
Specifications
Required
Power
(Steady
state)
500 mA @ 24 VDC
Required
Power
(Inrush)
30 A for 1 ms @ 24 VDC – DC Switched
2.5 A for 4 ms @ 24 VDC - AC Switched
Primary
Power
Range
10 – 30 VDC
Relative
Humidity
5 to 95% Non-condensing
Clock
Accuracy
+/- 35 ppm maximum at 25°
C
(+/- 1.53 Minutes per Month)
Operating
Temp
-10°C to +60°C
Display
Type
5.7” QVGA TFT
Display Size 5.7”
Display
Screen
Dimension
320 x 240
Display
Memory
2.75 MB
Display Life Minimum 40000 hours (50% brightness, 25 deg C)
User Keys 5 user-defined Function keys and a System Key
Screens
supported
1023
Colors 32768/ 16 shade Grey scale (XL6M models only)
Weight 26.5 oz. (.751 kg)
CE
UL
USA:
http://www.heapg.com/Pages/TechSupport/ProductCert.ht
ml
Europe:
http://www.horner-apg.com/en/support/certification.aspx
Connectivity
Serial Ports 2 Serial Ports – RS232 & RS485
Ethernet 10/100-Mbps (XL6e models only)
USB
USB Networking Port for communication with PCs, flash
device connectivity and programming Port
Removable
Media
Removable Media for upto 2 GB of storage for programs,
data logging or screen capture
Smartstix Remote IO modules communicating on CAN
2 Installation
1. Prior to mounting, observe requirements for the panel layout design and
spacing/clearances in the OCS XL6 Series Manual (MAN0883).
2. Cut the host panel.
3. Insert the OCS through the panel cutout (from the front). The gasket
material needs to be between the host panel and the OCS.
4. Install and tighten the mounting clips (provided with the OCS) until the
gasket material forms a tight seal.
5. Connect cables as needed such as communications, programming, power
and CsCAN cables to the ports using the provided connectors.
6. Begin configuration procedures.
3 Panel Cut-Out and Dimensions
Note: Max. panel thickness: 5 mm.
Refer to the User Manual (MAN0883) for panel box information and a checklist of requirements.
Mounting clips
XL6/XL6M/XL6e OCS Models
HE-XL100 / HE-XL1M0 / HEXT350C100 / HEXT280C100
HE-XL1E0 / HEXT351C100
Caution: Do
not
force the OCS into the panel cutout.
An incorrectly sized panel cutout can damage the
touch screen.
Note: The tolerance to meet NEMA standards is
±
0.005” (0.1 mm).
6.875
[175mm]
[131mm]
001OCS003-R1
5.156”
R .125” [3 mm] TYP.
RADIUS CORNERS
WHEN REQUIRING
DUST OR WATER
TIGHT SEAL PER
NEMA 4, 4X OR 12
001XLQX007
Vue de la page 0
1 2 3 4

Résumé du contenu

Page 1 - XL6/XL6M/XL6e OCS Models

MAN0884-04-EN Specifications / Installation ____________________________________________________________________________________________

Page 2

MAN0884-04-EN Specifications / Installation ____________________________________________________________________________________________

Page 3 - Signal Direction

MAN0884-04-EN Specifications / Installation ____________________________________________________________________________________________

Page 4

MAN0884-04-EN Specifications / Installation ____________________________________________________________________________________________