Specifications/Installation
MAN0971-02-EN
Cutout tolerance to meet NEMA standards
is ±0.005” (0.1mm). Max. Panel Thickness is 5mm.
XL7 OCS Datasheet for
HE-XW1E0, HE-XW1E2, HE-XW1E3, HE-XW1E4, HE-XW1E5
HEXT391C100, HEXT391C112, HEXT391C113, HEXT391C114, HEXT391C115
1. Specifications
2. Dimensions & Panel Cutout
Control & Logic Specifications
Required Power
170mA @ 24VDC Control Language Support
Full IEC 1131-3 Languages
7A for <1 ms @ 24 VDC
DC Switched
Logic Program Size
& Logic Scan Rate
Online Programming Changes
Supported in Advanced Ladder
I/O Support
Clock Accuracy
+/- 20 ppm maximum at 25
C
(+/- 1 Minutes per Month)
General Purpose Registers
50,000 (words) Retentive
16,384 (bits) Retentive
16,384 (bits) Non-retentive
UL / CE
USA: http://www.heapg.com/Pages/TechSupport/ProductCert.html
Europe: http://www.horner-apg.com/en/support/certification.aspx
Display Type 7” TFT Transmissive Color
1 RS-232 & 1 RS-485 on first Modular Jack (MJ1/2)
1 RS-232 or 1 RS-485 on second Modular Jack (MJ3)
USB 2.0 (480MHz) Programming & Data Access
USB 2.0 (480MHz) for USB FLASH Drives (2TB)
Remote I/O, Peer-to-Peer Comms, Cscape
User-Programmable Screens 1023 Ethernet
10/100 Mb (Auto-MDX), Modbus TCP C/S, HTTP, FTP,
SMTP, Cscape, Ethernet IP
SmartRail, SmartStix, SmartBlock, SmartMod
Screen Update Rate
User Configurable within the scan time.
(perceived as instantaneous in many cases)
MicroSD, support for 32GB max.
Application Updates, Datalogging, more
Input / Output Specifications
Model DC In
Relays HS In HS Out mA/V In
There are 4 high-speed inputs of the total DC Inputs. There are 2 high-speed outputs of the total DC
outputs. Model 2, 3 & 4 feature 12-bit Analog I/O. Model 5 features 14/16-bit Analog I/O. High-speed
Outputs can be used for PWM and Pulse Train Outputs, currently limited to <65kHz.
Pulse Measurement
2 Position Controlled Outputs
1 ON/OFF Setpoint per Output
Page 1 of 7