MAN0967-01-EN Specifications / Installation
__________________________________________________________________________________________________________________________________________________________________________
8/24/2012 #1037
1 Specifications
Specifications
Required
Power
(Steady state)
650 mA @ 24 VDC
1.3A @ 12 VDC
Required
Power
(Inrush)
25 A for <1 ms @ 24 VDC DC Switched
15 A for <1 ms @ 12VDC DC Switched
2.5 A for 1 ms @ 24 VDC - AC Switched
Primary
Power Range
10 30 VDC
Relative
Humidity
5 to 95% Non-condensing
Clock
Accuracy
+/- 35 ppm maximum at 25° C
(+/- 1.53 Minutes per Month)
Operating
Temp
-10°C to +60°C
Storage
Temp
-30°C to +70°C
Display Type
10.4” VGA TFT (550 nit typical)
Screen
Resolutions
640 x 480
Display
Memory
2.75 MB
Scan Rate
Controller 0.2 mS/K
Display Life
Minimum 50000 hours (50% brightness, 25 deg C)
User Keys
7 user-defined Function keys and a System Key
Screens
supported
1023
Colors
32768
Weight
70 oz. (2 kg)
CE / UL
USA:
http://www.heapg.com/Pages/TechSupport/ProductCert.
html
Europe:
http://www.horner-apg.com/en/support/certification.aspx
Connectivity
Serial
2 Serial Ports Each RS232 & RS485
Ethernet
10/100-Mbps Auto MDX
USB-A
For USB Flash Drives
USB-B
Mini B for connecting to PC (Programming, Envision)
Removable
Media
Removable Media for upto 2 GB of storage for programs,
data logging or screen capture
CAN
Remote I/O, Peer to Peer, PC, Programming
Remote I/O
SmartStix, SmartBlock, SmartMod or SmartRail
Local I/O
SmartStack
2 Installation
1. Prior to mounting, carefully plan the permanent location of the unit.
2. Cut the host panel.
3. Insert the OCS through the panel cutout (from the front). The gasket
material needs to be between the host panel and the OCS.
4. Install and tighten the mounting clips (provided with the OCS) until the
gasket material forms a tight seal.
5. Connect cables as needed such as communications, programming, power
and CsCAN cables to the ports using the provided connectors.
6. Begin configuration procedures.
3 Panel Cut-Out and Dimensions
Notes: Max. panel thickness: 5 mm.
Each SmartStack I/O module adds 0.75” (19mm) of depth
There are 10 mounting clip locations on the QX501.
For minimal mounting use four clips at 1, 2, 3 & 4 or 5, 6, 7 & 8.
For IP67 mounting use eight clips at locations 1 to 8.
For NEMA 4X mounting use ten clips in all locations.
The unit includes 8 clips order HE500ACC604 for additional clips
QX OCS
Datasheet
for
HE-QX501
Caution: Do not force the OCS into the panel cutout.
An incorrectly sized panel cutout can damage the
touch screen.
001OCS013
8.505
(216.0 mm)
11.360
(288.5 mm)
2.43” (61.7mm)
11.94(303.3mm)
9.08
(230.6mm)
9
1
2
5
6
3
4
10
7
8
Mounting Clip
Locations
Vue de la page 0
1 2 3

Résumé du contenu

Page 1 - Locations

MAN0967-01-EN Specifications / Installation ____________________________________________________________________________________________

Page 2

MAN0967-01-EN Specifications / Installation ____________________________________________________________________________________________

Page 3

MAN0967-01-EN Specifications / Installation ____________________________________________________________________________________________

Commentaires sur ces manuels

Pas de commentaire