MAN0886-04-EN Specifications / Installation
__________________________________________________________________________________________________________________________________________________________________
3/2/2010 Page 1 of 6 #1037
1 Specifications
Specifications
Digital DC Inputs XL103 XL104 Digital DC Outputs XL103 XL104
Inputs per Module
12 including 4 configurable
HSC inputs
24 including 4
configurable HSC
inputs
Outputs per Module
12 including 2 configurable
PWM outputs
16 including 2 configurable
PWM outputs
Commons per Module 1 Commons per Module 1
Input Voltage Range 12 VDC / 24 VDC Output Type Sourcing / 10 K Pull-Down
Absolute Max. Voltage 35 VDC Max.
Absolute Max.
Voltage
28 VDC Max.
Input Impedance
10 k
Output Protection Short Circuit
Input Current
Positive Logic Negative Logic
Max. Output Current
per point
0.5 A
Upper Threshold 0.8 mA -1.6 mA Max. Total Current
4 A Continuous
Lower Threshold 0.3 mA -2.1 mA
Max. Output Supply
Voltage
30 VDC
Max Upper Threshold 8 VDC
Minimum Output
Supply Voltage
10 VDC
Min Lower Threshold 3 VDC
Max. Voltage Drop at
Rated Current
0.25 VDC
OFF to ON Response 1 ms Max. Inrush Current 650 mA per channel
ON to OFF Response 1 ms Min. Load None
HSC Max. Switching Rate
10 kHz Totalizer/Pulse,Edges
5 kHz Frequency/Pulse,Width
2.5 kHz Quadrature
OFF to ON Response 1 ms
Analog Inputs, Medium
Resolution
XL103 XL104
ON to OFF Response 1 ms
Number of Channels 2 2
Output
Characteristics
Current Sourcing (Pos logic)
General Specifications
Input Ranges
Safe input voltage range
Input Impedance
(Clamped @ -0.5 VDC to 12
VDC)
0 - 10 VDC
0 – 20 mA
4 – 20 mA
-0.5 V to +12V
Current Mode:
100
Voltage Mode:
500 k
Required Power
(Steady State)
500 mA @ 24 VDC
Required Power (Inrush)
30 A for 1 ms @ 24 VDC – DC Switched
2.5 A for 4 ms @ 24 VDC - AC Switched
Nominal Resolution
%AI full scale
Max. Over-Current
10 Bits
32,000 counts
35 mA
Primary Power Range 10 – 30 VDC
Conversion Speed All channels converted once per ladder scan Relative Humidity 5 to 95% Non-condensing
Max. Error at 25°C (excluding
zero)
4-20 mA 1.00%
0-20 mA 1.00%
0-10 VDC 0.50%
Operating Temperature
-10°C to +60°C
Terminal Type Screw Type,5 mm Removable
Additional error for
temperatures other than 25°C
TBD
CE
UL
USA:
http://www.heapg.com/Pages/TechSupport/ProductCert.html
Europe:
http://www.horner-apg.com/en/support/certification.aspx
Filtering
160 Hz hash (noise) filter
1-128 scan digital running average filter
Weight 26.5 oz. (.751 kg)
Clock Accuracy
+/- 35 ppm maximum at 25° C
(+/- 1.53 Minutes per Month)
Display Properties
Display Type 5.7” QVGA TFT
Display Life Minimum 40000 hours (50% brightness, 25 deg C)
Display Size 5.7” 5.7”
User Keys 5 user-defined Function keys and a System Key
Display Screen Dimension 320 x 240
Screens supported 1023
Display Memory 2.75 MB
Colors 32768/ 16 shade Grey scale (XL6M models only)
Connectivity
Serial Ports 2 Serial Ports – RS232 & RS485
Ethernet 10/100-Mbps (XL6e models only)
USB USB Networking Port for communication with PCs and programming Port
Removable Media Removable Media for upto 2 GB of storage for programs, data logging or screen capture
Smartstix Remote IO modules communicating on CAN
Note: Highest usable frequency for PWM output is 65 KHz
XL6/XL6M/XL6e OCS Models
HE-XL103 / HE-XL1M3 / HEXT350C113 /
HEXT280C113
HE-XL1E3 / HEXT351C113
Digital DC Inputs / 12 Digital Outputs
2 Analog Inputs (Medium Resolution)
XL6/XL6M/XL6e OCS Models
HE-XL104 / HE-XL1M4 / HEXT350C114 /
HEXT280C114
HE-XL1E4 / HEXT351C114
24 Digital DC Inputs / 16 Digital Outputs
2 Analog Inputs (Medium Resolution)
Vue de la page 0
1 2 3 4 5 6

Résumé du contenu

Page 1 - XL6/XL6M/XL6e OCS Models

MAN0886-04-EN Specifications / Installation ____________________________________________________________________________________________

Page 2 - 001XLQX007

MAN0886-04-EN Specifications / Installation ____________________________________________________________________________________________

Page 3 - Remove cover

MAN0886-04-EN Specifications / Installation ____________________________________________________________________________________________

Page 4 - Signal Direction

MAN0886-04-EN Specifications / Installation ____________________________________________________________________________________________

Page 5 - 10 - 30VDC

MAN0886-04-EN Specifications / Installation ____________________________________________________________________________________________

Page 6

MAN0886-04-EN Specifications / Installation ____________________________________________________________________________________________

Commentaires sur ces manuels

Pas de commentaire