Specifications/Installation
MAN0971-02-EN
Model 5 I/O
The XL7 model 5 (HE-XW1E5) features 12 DC Inputs, 12 DC outputs, with high performance, highly configurable Analog Inputs (2) and
Analog Outputs (2). , The DC Inputs are 12/24Vdc compatible, and can be jumpered for Positive Logic (sinking), or Negative Logic
(sourcing). Two of the inputs (H1-H2) can be used for high-speed functions up to 500kHz. The 12/24VDC Outputs feature Electronic Short
Circuit protection, and support currents up to 0.5A per point, and 4A total. Two of the DC Outputs can be used for high speed functions
(PWM or PTO). The output frequency is limited by the switching capability of the output drivers (about 10kHz), although an optional
accessory (HE-XHSQ) can be added to provide parallel output drivers supporting frequencies up to 200kHz.
The two high resolution Analog Inputs can be configured for 4-20mA, 0-10V, or 0-100mV at 14-bit resolution. They also can be configured
for 16-bit temperature measurement supporting Thermocouples or RTDs with 0.05°C resolution. The Analog Outputs are sourcing, and
can be configured for 4-20mA or 0-10V at 14-bit resolution. Each Analog Input or Output channel can be configured independently for
maximum flexibility.
Page 7 of 7