MAN0890-02-EN CH. 14
August 20, 2009 Page 83 of 96 ECN # 979
14.5 AutoRun
This system menu option, when enabled (YES), allows the user to automatically place the OCS into RUN
mode after the AutoLoad operation or automatic Restore Data operation.
Figure 14.11 – Enable AutoRun System Menu
When the AutoRun setting is disabled (NO), the OCS remains in the IDLE mode after a Restore Data or
AutoLoad operation.
%SR164.5 can be set by putting the system into RUN mode automatically, once an AutoLoad has been
performed or an Auto-Restore has occurred.
If for any reason the AutoLoad-Run (Loading the AUTOLOAD.PGM automatically and OCS put in RUN
mode) sequence does not succeed, a pop-up message box saying "AUTO-LOAD-RUN SEQUENCE
FAILED" will be displayed. It will also show the reason for its failure. On acknowledging this message box
the AutoLoad-Run sequence will be terminated, controller will return to the first user-screen and will be
placed in IDLE mode.