MAN0893-02-EN Specifications / Installation
________________________________________________________________________________________________________________________________________
Feb 2, 2010 Page 3 of 5 #1039
4.1
Serial Communications
:
MJ1: (RS-232 / RS-485) Use for Cscape programming and
Application-Defined Communications.
MJ2: (RS-232 / RS-485) Use for Application-Defined
Communications.
Pin
MJ1 Pins MJ2 Pins
Signal Direction Signal Direction
8
TXD OUT TXD OUT
7
RXD IN RXD IN
6
0 V Ground 0 V Ground
5*
+5 60mA OUT +5 60mA OUT
4
RTS OUT TX- OUT
3
CTS IN TX+ OUT
2
RX- / TX- IN / OUT RX- IN
1
RX+ / TX+ IN / OUT RX+ IN
1
8
Pin
MJ2 Pins
Signal Direction
8
TXD OUT
7
RXD IN
6
0 V Ground
5*
+5 60mA OUT
4
TX- OUT
3
TX+ OUT
2
TX-/RX- IN/OUT
1
TX+/RX+ IN/OUT
1
8
MJ2 Half Duplex Mode
* +5V 60mA Max
Pin
MJ2 Pins
Signal Direction
8
TXD OUT
7
RXD IN
6
0 V Ground
5*
+5 60mA OUT
4
TX- OUT
3
TX+ OUT
2
RX- IN
1
RX+ IN
1
8
MJ2 Full Duplex Mode
* +5V 60mA Max
MJ1
Power
CAN
MJ2
DIP Switches
Smart Stack Connector
(2 smartstack modules
supported)